![]() ![]() | The IRIS uniscan is a fail safe flame monitor and amplifier, mounted completely into one enclosure. Its purpose is to monitor gas or oil flames in process heaters, or the smaller utility boilers.
The operating voltage range is 18 to 27 VDC, so that losses or fluctuations in the voltage have no effect within these parameters.
The flame on output is a 24 VDC signal. There is also a 4 to 20 mA analogue signal output, suitable for driving a flame signal meter, or chart recorder.
As well as gain and drop out time adjustments a high band pass filter with four positions is provided for better discrimination.
A DIN rail mounting power supply module, to provide a 24VDC output from a 115/230 VAC input is available if required.
A commissioning module is also available. It is battery powered, and is capable of powering the UNISCAN on the boiler front for approx. one hour. This enables an evaluation on performance, without the need for separate power supplies and wiring. - housing EEx - d or IP65 - 100 % fail safe and self checking |
| MODEL | IRIS UNISCAN EEx - d or IP 65 |
| DESCRIPTION | Flame Monitor and Amplifier |
| EXECUTION | - CENELEC APPROVED - EXPLOSION PROOF HOUSING for CL.1 DIV.2 T6 HAZARDOUS AREA - IP 66 CENELEC -- INERIS 03ATEX0175X |
| FAIL SAFE | YES, 100% |
| SELF CHECKING | YES, ELECTRONIC SWITCHING |
| WAVES SPECTRUM DETECTED | 750 - 1900 nm NANOMETER |
| SUPPLY VOLTAGE | - 24 VDC + 10% -25% - separate module available with 110 or 240 VAC primary and 24 VDC secondary |
| OUTPUT | one normally open volt powered 24 VDC contact for flame on (SPST) |
| TRANSMISSION | NO LIMIT providing supply cable is sized correctly |
| CABLE | normally 5 core 1sqmm with PVC outer sheeth (or 4 core with overall screen) |
| CONNECTION | via AMPHENOL PLUG - socket on rear of enclosure |
| FLAME DROP OUT TIME | SELECTABLE to 1 - 2 or 3 seconds |