The IRIS Model P520 is a state of the art flame signal processor. It is designed to be used with the IRIS 500 flame monitoring viewing heads. The P520 microprocessor controlled device does the same thing as the Model 500, but does it much better. It is possible, for example to program the FLAME ON and FLAME OFF set-points locally (from the front panel) or remotely (from a host computer). The P520 communicates with the remote computer through its RS-232 serial port at 4800 baud, or RS 422 differential port. The front panel of the P520 plug-in module is shown on the back page. Note the two LED (light emitting diode) displays; a four digit readout, and a bar graph, both representing flame signal strenght. In addition there are three discrete LEDs and 11 push button switches.
- Front panel or rack installation
- 100 % fail safe and self checking

DESCRIPTIONFlame signal processor
ELECTRICAL

INPUT POWER
(with one V.H.)



26VDC + 5% -20%, 300 mA
(100 mA for each additional V.H.)

ENVIRONMENTAL

Ambient Temperature



0 ƒC to +50 ƒC

CABLE

(Between Viewing Head and Signal Processor)



4 conductor, #18AWG, one wire shielded with braided shield for flame signal

OUTPUT

Flame Relay
Self-Checking Relay




Analog Flame Signal

Power to Viewing Head



2 From C Contacts
1 From C Contact
Contact Ratings:
Max switching power 60W 100VA
Max switching voltage 220V AC, DC
Max switching current 2A
0 to 20 mA current output for remote meters,
360 ohm max resistance
+26 VDC, fused .25A
+14.3 VDC Pulsing .2 Sec ON .8 Sec OFF

INPUT

Channel Select
(Isolated Input)

Flame Signal from V. H.
(Isolated Input)



V in 7.5 - 30 VDC range (Input R = 3900 ohms)
26 VDC, 6.4 mA
10 VDC, 2.3 mA
Vin 7.5 - 30 VDC range (Input R = 3900 ohms)
13.6 VDC, 3.2 mA

SERIAL COMMUNICATION

RS - 232 COM port on personal computer
at 4800 Baud

RS - 422 (Differential) on IRIS P520
at 4800 Baud



Input / Output serial communication between PC and IRIS P520

Input / Output circuits photocoupler isolated from P520 power supplies and ground