| MODEL | IRIS 500 IRX2 EEx - d or IP 65 |
| DESCRIPTION | Flame Detector Unit |
| EXECUTION | - CENELEC APPROVED - EXPLOSION PROOF HOUSING for CL.1 DIV.2 T6 HAZARDOUS AREA - IP 66 |
| FAIL SAFE | YES, 100% |
| SELF CHECKING | YES, ELECTRONIC SWITCHING |
| COMPONENTS CHECKING TIME | for 200 mseconds every 1 second |
| WAVES SPECTRUM DETECTED | 340 - 3000nm NANOMETER HIGH FREQUENCY INFRARED FLICKER (four positions selectable filter) |
| OPTICAL | IR LENS |
| TRASMITTANCE | 209 - 3600 nm |
| ANGLE OF VIEW | 2.7 maximum |
| CONNECTION TO THE BURNER | 1" NPT F |
| PURGE AIR CONNECTION | 1/2" NPT F |
| PURGE AIR FLOW REQUIRED | 0.5 NCM/H |
| ELECTRICAL CONNECTION | 3/4" NPT F |
| CABLE GLAND | DOUBLE COMPRESSION TYPE for ARMOURED CABLE |